DC 1.3
Data Center
information
Gross size
23,500 m²
Net size
5,500 m²
Power available
2 x 10.0 MVA
IT room height
3.80 m
Raised floor
1.00 m
Floor load
2,000 kg/m²
Equipment elevator
2,500 kg
UPS systems
Redundant 2 x (N+1)
Generator autonomy
48 hours; 24/365 refuel contracts
Power to IT rooms
Average = 1200 W/m²
Power loads
up to 10 kW/rack
Server room temperature
18-27° C - ASHRAE TC9.9 Class A1 recommended
Cooling redundancy
2 x N, N + 1
Cooling specifications
Water input 15° C; output 21° C
PUE
1,2 / 1,3
SLA
99.75% / 99.995%
SECURITY & ACCESS
- Fire and very early smoke detection (VESDA)
- Neutral gas (nitrogen) fire suppression system
- Water leakage detection
- Intrusion detection
- 24/7/365 on-site security guards with controlled access
CONNECTIVITY
- Carrier-neutral
- International & national telecom operators
- Internet exchanges hosted at LuxConnect: NL-ix & LU-CIX