DC 1.3
Technical
Image
Adresse
202, Z.A.E. Wolser F, L-3290 Bettembourg
Operational since
mid-2015
- Uptime Tier IV certified
- 100% renewable energy sources
- Electromagnetic protection concept
- Remote central monitoring of all technical systems
Data Center information
Image
Gross size
23 500 m²
Net size
5 500 m²
Power available
2 x 10.0 MVA
IT Room height
3,76 m
Raised floor
1 m
Floor load
2 000 kg/m²
Equipment elevator
2 500 kg
UPS systems
Redundant 2 x (N+1)
Generator autonomy
48 hours; 24/365 refuel contracts
Power to IT rooms
Average = 1200 W/m²
Power loads
up to 10 kW/rack
Server room temperature
18-27° C - ASHRAE TC9.9 Class A1 recommended
Cooling redundancy
2 x N, N + 1
Cooling specifications
Water input 15° C; output 21° C
PUE
1,3
SLA