DC 1.2
Technical
Image
Adresse
202, Z.A.E. Wolser F, L-3290 Bettembourg
Operational since
January 2011
- Tier IV
- 100% renewable energy sources
- Electromagnetic protection concept
- Remote central monitoring of all technical systems
Data Center information
Image
Gross size
4 500 m²
Net size
1 300 m²
Power available
2 x 6.3 MVA
IT Room height
3,6 m
Raised floor
1 m
Floor load
2 000 kg/m²
Equipment elevator
2 500 kg
UPS systems
Redundant 2 x (N+1)
Generator autonomy
48hours; 24/365 refuel contracts
Power to IT rooms
Average 2,300 W/m²
Power loads
up to 10 kW/rack
Server room temperature
18-27° C - ASHRAE TC9.9 Class A1 recommended
Cooling redundancy
2 x N
Cooling specifications
Water input 10° C; output 15° C
PUE
1.45
SLA
99,995 %